Multiple Pumps in Parallel
Cycle Stop Valves can solve the problems associated with using multiple pumps in
parallel. Most of the time one of the pumps will build slightly higher pressure than
the other pump or the static water level in one well is slightly higher than in the
other well. This causes the pump that builds the most pressure, even if it is only 1
PSI more, to create a dead head situation for the other pump. At a low flow rate
the two pumps are working against each other and the pump that builds the least
pressure will be destroyed due to a lack of cooling flow. This is one reason we do
not recommend using a single Cycle Stop Valve for two or more pumps unless only
one of the pumps is operated at any given time.
When a Cycle Stop Valve is placed on the discharge of each pump before the lines
manifold together, back pressure from the second pump does not affect the first
pump. Each pump is then working against it's own back pressure. The non closing
feature of the Cycle Stop Valve insures a minimum flow to keep each pump cool,
because the back pressure or inlet pressure to the Cycle Stop Valve is higher than
the outlet or system pressure.
Multiple pumps can be the most efficient way of supplying water. Systems with a
wide variation in flow can benefit greatly from being able to utilize the pump or
pumps that can best meet the particular flow required. Using a Cycle Stop Valve
on each pump allows multiple pumps to operate in parallel safely and efficiently.
The following are examples of how Cycle Stop Valves can control different type of
multiple pump systems.
Some systems use multiple pumps that are sitting side by side and pumping from
the same water source to a common system. Other systems may use multiple
pumps located in different locations and pumping from different water sources to
a common system. Each pump needs it's own Cycle Stop Valve, check valve, and
pressure switch. If the pumps are located in different locations, a small pressure
tank is needed for each pump. If the pumps are located together they can use a
single pressure tank plumbed to the common discharge of all Cycle Stop Valves. All
of the pressure switches should be in a manifold together with the small line that
enters the pressure tank. Once installed in this way the only connection between
the pumps is that they pump into a common manifold and run on staggered pressure
settings.
For this example we will use a three pump system having a small, medium, and a
large pump. A minimum of 40 PSI is required at all times and the large pump is set
to come on at 40 PSI and off at 50 PSI. The medium pump comes on at 50 PSI and
off at 60 PSI. The small pump will come on at 60 PSI and if the system flow ever
gets below 5 GPM this pump will shut off at 70 PSI. Usually these large systems
have more than 5 GPM leaking so the small pump will run continuously and it's Cycle
Stop Valve will hold the system at a constant 60 PSI. The Cycle Stop Valves on
multiple pump systems should be adjusted to hold pressure constant at the same
pressure as its' pump starts.
When flow increases and the small pump is no longer able to keep up, the pressure
will drop from 60 PSI to 50 PSI and the medium pump is started. The Cycle Stop
Valve on this pump maintains 50 PSI until flow increases beyond the capabilities of
the first two pumps. The pressure then drops to 40 PSI and the large pump is
started. The Cycle Stop Valve on the large pump will keep the system pressure at
40 PSI as long as the amount of water needed can be produced by the three
pumps. When the system flow is decreased to a point that can be supplied by the
small and medium pump, the Cycle Stop Valve on the medium pump will bring the
pressure up to 50 PSI and the large pump is shut off. If the system flow
continues to decrease to a point that can be supplied by the small pump, the Cycle
Stop Valve on the small pump will bring the pressure up to 60 PSI and the medium
pump is also shut off. The Cycle Stop Valve on the small pump will maintain 60 PSI
supplying the leaks and small demands in the system. Only if there is zero flow will
the Cycle Stop Valve on the small pump allow the system to increase to 70 PSI and
the small pump is shut off. A pressure relief valve set at 75 PSI can be used for a
safety. The largest pump runs at the lowest pressure of 40 PSI, therefore the
tank should be precharged with air to 35 PSI.
These pumps can be sitting side by side or they can be miles apart. The staggered
pressure settings makes all pumps work together when needed. There is no need
for wires or radio controls between pumps. Even pumps that are miles from each
other operate on system pressure only. If the pump that is running cannot keep up
with the demand, the system pressure drops slightly and the next pump required is
started by its' own pressure switch. As demand decreases, system pressure
increases and pumps that are no longer needed are shut down by there own
pressure switch. Cycle Stop Valves allow simple, safe, and efficient use of multiple
pumps in parallel.
|