|
|
Using Ground Storage Tank Instead of Pressure Tanks for Low Flow in Big Systems
There are other ways of handling continuous low flow in systems where there is no place
to install a small Pressure Maintenance pump. An example would be a system with a
water source being a single water well with a 100 HP pump. When used with a Cycle
Stop Valve the 100 HP would be able to supply a demand as small as 5 GPM without
causing damage to the pump or the system. However, the 100 HP pump when restricted
would only drop to about a 60 HP load. While the 5 GPM flow will not hurt the pump or
motor in any way, it is not very efficient to use 60 HP to pump 5 GPM. Therefore,
another option is recommended. For this example we are going to start the 100 HP at
50 PSI and turn it off at 60 PSI. The Cycle Stop valve will also be set at 50 PSI. The
100 HP and it’s Cycle Stop Valve will feed from 5 GPM to 2,000 GPM into the system
while maintaining 50 PSI. The only way the 100 HP will be shut off is if the flow rate
being used is less than 5 GPM. Then 5 GPM will enter a small pressure tank until the
pressure reaches 60 PSI and the 100 HP will be shut off. This is never going to happen
because the system is large enough that there is about 10 GPM minimum flow at all
times.
We can still install a PM pump. Somewhere in the distribution system, it can be past
the controls at the 100 HP well or anywhere along the pipe line, a ground storage tank
is needed. For this example we are going to use a 3,000 gallon atmospheric tank tied
into the main line 100 yards from the supply well. A 3" solenoid valve is used to fill the
3,000 gallon tank. The solenoid valve is opened by a low probe and closed by a high
probe in the tank. Drawing water out of the 3,000 gallon tank is a 3 HP 50 GPM PM
pump. The PM pump is controlled by a Cycle Stop Valve and a pressure switch with a
small pressure tank. The PM pump starts at 60 PSI and is turned off at 70 PSI. The
Cycle Stop Valve on the PM pump maintains 60 PSI when usage is between 5 GPM and 50
GPM. The PM pump simply discharges into the main line. When the 3,000 gallon storage
tank is full and usage is less than 50 GPM the 3 HP pump is the only pump running.
When the 3,000 gallon tank is empty the low probe would shut off the PM pump and
open the solenoid valve at the same time. The pressure would drop to 50 PSI and the
100 HP would be started. The Cycle Stop Valve on the 100 HP would hold the system at
50 PSI matching the usage in the system while refilling the 3,000 gallon tank. When
the storage tank is full and the top probe is reached the solenoid valve would shut and
the PM pump would be restarted. If the usage is less than 50 GPM the PM pump will be
able to bring the system pressure up to 60 PSI which would shut off the 100 HP pump.
If usage is above 50 GPM the PM pump will not be able to bring the system pressure up
to 60 PSI. The Cycle Stop Valve on the 100 HP will maintain 50 PSI and add only what
extra water is needed above what the 3 HP cannot produce. As long as the usage
remains below 50 GPM the 100 HP pump only comes on to refill the 3,000 gallon tank as
needed.
|