Cycle Stop Valves
Constant Pressure Pump Control Valves
Home Products Animations Forum FAQ Order Online  


Reviews
CSV Applications
Product Catalog
Print Literature
Well and Pump Basic Info
VFD Does Not Save Energy
CSV vs VFD
CSV Tech. Info
WQA Certified
Calculators
Tank Sizing
Pump & Motor Manufacturers
Letters to Editor
Retrofits
Pressure Switch
Event Calendar
Warranty Info
About Us
PK1A Pside-kick® Troubleshooting

SymptomCauseRemedy
Pump is cycling off and on Pressure switch or CSV1A valve not set correctly Cut off pressure must be higher than CSV1A pressure. Increase pressure switch cut off or decrease CSV1A valve setting.
Waterlogged pressure tank Replace pressure tank
Bad or torn diaphragm in CSV1A Replace diaphragm.
Manifold not assembled correctly Verify assembled as instructed
Low Pressure Demand is more than pump can provide at current pressure setting Reduce demand so it is within pump capabilities to maintain desired pressure.
CSV1A is not set correctly Reset CSV1A. (Turn adjust stem clockwise to increase psi and counter clockwise to decrease psi)
Chattering Too much air in tank Reduce air pressure in tank to 5-7 PSI below pressure switch cut in pressure.
CSV1A setting is too close to pressure switch cut off pressure Set pressure switch cut off pressure at least 10 PSI higher than CSV1A setting.
Pump rapid cycles at start up and then begins to function correctly Air pressure in tank too high Reduce air pressure in tank to 5-7 psi below cut in pressure.
Multiple check valves in system working against each other Remove all but the check valve or foot valve on the pump itself.
Cycle Stop Valves® is a registered trademark.
All right reserved unless prior authorization is obtained.
Cycle Stop Valves, Inc.
10221 CR 6900
Lubbock, Texas 79407
Send Email
800-652-0207
Fax: 806-885-1994