|
|
What They Don't Want You to Know About Variable Speed Pumps
Excessive use of energy is an ailment that we desperately want to cure. Those
afflicted with this syndrome are so eager for a cure that they can be easily
mislead with promising treatments. Many articles claim that the variable speed
drive is the magic pill that cures excessive energy consumption. As with any
medication, you should carefully read the fine print. You may find that variable
speed drives used with pumps do not save energy. Drives may also cause side
effects that can far outweigh any possible benefits.
One recent article explains why variable speed pumps do not save energy. This
article talks about the fact that losing head by the square of the speed can have
more of an impact on pumping applications than reducing horse power by the cube
of the speed. Another recent article says that variable speed drives save so much
energy that it is worth putting up with all the technical problems and side effects.
A third article claims that variable speed drives have already saved so much energy
that they have cut CO2 emissions by up to 400 million tons compared to pumps
using throttling valves as control. Because of misleading articles, many people have
become victims of hype and hysteria, myths and legends, or just false information.
Doing the math ourselves is not difficult and is apparently the only way to uncover
the truth.
With a simple pump curve, you can compare throttling with a valve to variable speed
control. If you are stuck with an existing, oversized, or badly designed pump, a
variable speed drive may be able to save some energy in low flow conditions. With
compressors, fans, conveyor belts, positive displacement pumps, and other
applications, variable speed drives might be worth putting up with, and can possibly
save energy. If a system requires the pressure to increase as flow increases, real
power savings could be had from increasing the pipe size, which will allow you to
reduce the pump size. If you are able to show energy savings using variable speed
to hold a constant pressure or TDH on a centrifugal pump, someone should have
done the math before the pump was chosen. Any pump with a centrifugal impeller
that has a good brake horse power curve will save as much if not more energy when
controlled with a throttling valve than when controlled with a variable speed drive.
Throttling valves do not burn energy as many drive manufacturers would like for
you to believe. As back pressure on the pump increases from throttling with a
valve, the horse power or power consumption decreases. This is a "counter
intuitive" property of a centrifugal impeller. Many people falsely believe that
choking back a pump will make it work harder. Choking a pump actually makes it
work easier as the power consumption is proportional to the flow rate and inversely
proportional to the back pressure.
Be wary of drive manufacturers or so called "smart pumps and controls" who will
try to tell you that valves waste or burn energy. Some will even compare valve
control to driving a car with one foot on the gas and one foot on the brake. These
people obviously do not understand how pumps work. Since there are many other
good uses for variable speed controls besides centrifugal pumps, they should not
have to resort to false information to sell drives.
Most pump curves include a brake horse power curve. With these horse power
curves you can easily see that as flow decreases, horse power also decreases. If a
horse power curve is not available you can do the math with the following horse
power calculation that has been used for generations.
With this calculation or the horse power curve you will see that when throttling a
pump, even when efficiency drops to 5%, horse power can still decrease by about
50% of the maximum horse power.
To do the math with the variable speed controller you will need to use the Affinity
Law. However, you can make a huge mistake in focusing on the power savings by
the cube of the speed, when the most important part of the Affinity Law is that
head is reduced by the square of the pump speed. First you must determine the
minimum RPM that the pump can spin and still produce the head required before
you can use the Affinity Law. The following is a simple calculation to help you
determine the minimum possible pump speed. Once the minimum possible pump
speed is determined, then the cube of that number will give you the Minimum
Possible Horse Power using a variable speed drive.
Total Dynamic Head or (TDH) determines the minimum possible speed. Divide the
(TDH) by the pumps Shut Off Head (SOH). The answer will be a percentage of
head loss possible or Possible Head Reduction (PHR). Minimum Possible Speed or
(MPS) squared equals the Possible Head Reduction (PHR). (MPS) cubed equals the
minimum percentage of Horse Power or Minimum Possible Horse Power (MPHP).
Another common mistake is not to give the centrifugal pump credit for it's natural
brake horse power characteristics. All of the articles you have read that show a
pump saving large amounts of energy using variable speed compared to a throttling
valve have made these mistakes. The fact that we are using a pump means we must
need to produce a certain amount of head. An example would be pumping over a
mountain that is 231 feet high. The flow rate could vary from a little to a lot but
we always need 231 feet TDH to get the flow over the mountain. Using the
calculation above for a pump that has a Shut Off Head (SOH) of 285 feet, we can
only reduce the RPM by 9% and still produce enough head to get the flow over the
231 foot mountain. Slowing a pump by only 9% reduces the speed of a 3550 RPM
pump to only 3280 RPM. Any slower than 3280 RPM and the pump will not produce
enough head to get any water to the top of the mountain. According to the
Affinity Law, reducing the speed by 9% only reduces the power required by 25%.
The Affinity Law would then reduce the power consumption of a 100 HP pump to 75
HP, not 1 HP as many drive companies would like for you to believe. Using a
throttling valve will maintain the head at 231 feet as required while throttling the
full speed pump back to low flow reduces the 100 HP load to 42 HP. Unless we
can change the TDH required, which would mean changing the height of the
mountain, variable speed control for this pump will only save a tiny amount of
energy over the same pump simply throttled with a valve.
Maintaining the Total Dynamic Head required is the most important function of a
pump. The curves in many articles show the head drop from 10 to 7, or 200 feet to
140 feet. This is a typical case of not being able to see the forest for all the
trees in the way. Even the so called experts forget that head is lost by the
square of the speed. This limits the effectiveness of drives and makes the energy
calculations in most articles completely incorrect.
With a variable speed drive there are many negative side effects. Pulsing DC
voltage creates high voltage spikes in the motor. EDM currents build up in the
rotor and discharge through the ball bearings causing damage from electrical
fluting. Certain critical speeds cause pump and motor vibration. Harmonics are
created and fed back into the electrical grid. Radios, cell phones, and other
electronics can be negatively affected by RF interference created by the drive.
Three percent of energy is also wasted due to losses in the drive itself.
Considerable technical assistance may be required. I have even seen in hot
climates where the air conditioning system needed to keep the drive cool, uses as
much energy as the pumps themselves. Drives are computers with a
microprocessor base. Parts needed to repair a five year old drive are no more
available than parts for any other five year old computer. Many articles state that
the expense and side effects or the "myths and legends" are worth putting up with
because of the energy savings. However, if there are very little or NO energy
savings, all of these side effects can be eliminated by using other simpler and less
expensive controls such as a throttling valve. Even if energy savings can be shown
using a variable speed at low flow, at maximum flow losses in the drive itself adds
three percent more energy needed than if the pump were running on an across the
line panel. If any energy savings are present, they can be so small that it takes
many years to get a payback instead of the few months that we were promised.
(See following curve)
Example from curve:
231' TDH, 1200 GPM 6 hours per day, 100 GPM 6 hours per day at $0.12 per KW hour, 100 HP drive cost $10,000.00
KW to run pump with valve:
1 KW per HP X 100 HP X 6 hours = 600 KWhrs.
1 KW per HP X 42 HP X 6 hours = 252 KWhrs.
Total 852 KWhrs.
KW to run pump with drive:
1 KW per HP X 103 HP X 6 hours = 618 KWhrs.
1 KW per HP X 38 HP X 6 hours = 228 KWhrs.
Total 846 KWhrs.
Cost of running pump with valve control:
852 X .12 = $102.24 per day
Cost of running pump with drive control:
846 X .12 = $101.52 per day
Cost difference of running valve and drive = $0.72 per day
Drive cost $10,000.00 divided by $0.72 = 13,888 days or 38 years to pay off
drive if the pump is used everyday of the year. If the pump is only used for six
months out of the year it will double the pay out time of the drive to 76
years. If you are paying less than twelve cents a kilowatt, it will take even
longer to pay off a drive. When it takes longer than 10 years to get a payback, the
drive itself may not last long enough to ever recuperate it's own expense.
Another argument you will hear is that variable speed drives eliminate end rush
current compared to across the line starting. While this is true, the only time this
matters is when the pump is started. When a valve is throttling the flow from a
pump to match the usage, cycling on and off is eliminated and end rush currents do
not come into play. On smaller systems that do occasionally require a zero flow
rate, the starting and stopping is also minimal and end rush current is not
important. Throttling valves can also be used with soft start panels when needed
to reduce end rush currents. The older style reduced voltage soft starters will
still eliminate end rush currents. Auto transformer soft starters will do away with
the negative side effects that come with the new style electronic soft starters
and variable speed drives.
Many people also believe that throttling is bad for pumps. The truth is, pumps that
cannot handle throttling have been built for planned obsolescence and are cheaply
designed. Pumps with slightly stronger shafts and bearings can easily handle
throttling. As long as a small cooling bypass flow is maintained, especially when
pumping fairly cool water, there is no heat buildup from throttling. Contrary to
what some people were taught, recent studies also show that vibration in some
pumps actually decreases with throttling. Modern constant pressure valves have
also eliminated screens, shafts, and speed controls. This makes a simple,
dependable throttling valve even more dependable.
The multitude of technical aspects of using a variable speed drive can be baffling.
A simple pump system is a dependable pump system. Don't allow sales tactics that
falsely claim energy savings talk you into spending more money and having more
headaches by using drives. Do the math yourself. Talk to people who have
experience with both variable speed drives and throttling valves. Take advantage
of the natural characteristics of a centrifugal pump that causes horse power to
decrease as flow decreases. A variable speed drive can be a complicated way of
trying to trick a pump into doing something that a pump already does naturally.
Anyone who truly understands centrifugal pumps and their relationship to variable
speed would never claim energy savings compared to throttling valves. Those that
do understand are trying to complicate the issue to keep you from finding out what
they don't want you to know.
|